KYN28A-12 Metal-Clad Withdrawable Switchgear for Indoor MV Distribution

KYN28A-12 is an indoor metal-clad withdrawable switchgear for medium-voltage power receiving and distribution. Use it where VCB trucks, compartment separation and relay protection access are required.

3.6 / 7.2 / 12 kV3 / 6 / 7.2 / 12 / 24 kV ratings630 A to 4000 AIP4X / IP2X
KYN28A-12 ratings3.6 kV, 7.2 kV and 12 kV indoor MV switchgear ratings.
630 A to 4000 ARated current range with 16 kA to 50 kA 4 s short-time withstand classes.
Busbar to 6300 AExtended KYN28 ratings include main and branch busbar classes up to 6300 A.
Series and rating data

KYN28A-12 Ratings and Extended KYN28 Specifications

Review KYN28A-12 ratings, extended KYN28 specifications and cabinet construction before confirming voltage class, busbar current, short-circuit level and VCB model. The KYN28A-12 table references IEC 62271-200, IEC 62271-100 and GB3906.

KYN28 front cabinet lineup with relay and breaker compartments
KYN28A-12 ratings

KYN28A-12 AC Metal-Enclosed Switchgear

Indoor air-insulated metal-clad withdrawable switchgear for receiving, distributing, protecting and monitoring three-phase medium-voltage circuits.

3.6/7.2/12 kV630 A to 4000 A50/60 Hz

Use this rating table for conventional indoor 12 kV switchgear rooms with withdrawable VCB trucks.

KYN28 indoor metal-clad withdrawable switchgear cabinet lineup
Extended KYN28 ratings

KYN28 3-24 kV Indoor Metal-Clad Switchgear

Extended KYN28 ratings cover 3 kV to 24 kV voltage classes, insulation withstand values, busbar current classes and cabinet weight.

3/6/7.2/12/24 kVBusbar to 6300 A1000 kg

Use this rating data when the specification includes 24 kV class or busbar current above 4000 A.

KYN28 compartment interior view with withdrawable breaker and relay chamber
Cabinet construction

KYN28 Withdrawable VCB, Relay Chamber and Interlock System

The KYN28 structure combines a metal-clad body, withdrawable breaker truck, relay chamber, cable compartment and safety interlocking.

Metal-clad bodyWithdrawable VCBFive-anti interlock

Confirm breaker model, relay protection, metering and cable entry before cabinet layout.

KYN28A-12 ratings

KYN28A-12 AC Metal-Enclosed Switchgear Specifications

Indoor air-insulated metal-clad withdrawable switchgear for receiving, distributing, protecting and monitoring three-phase medium-voltage circuits.

Product nameKYN28A-12 AC metal-enclosed switchgear
Rated voltage3.6 kV, 7.2 kV, 12 kV
Rated current630/1250/1600/2000/2500/3150/4000 A
4 s short-time withstand current16/20/25/31/31.5/40/50 kA
Rated peak withstand current50/63/80/100/125 kA
Rated frequency50/60 Hz
Voltage levelMedium voltage
PhaseAC 3 phase
Protection levelEnclosure IP4X; each compartment partition IP2X
StandardsIEC62271-200; IEC62271-100; GB3906
Extended KYN28 ratings

KYN28 3-24 kV Indoor Metal-Clad Switchgear Specifications

Extended KYN28 ratings cover 3 kV to 24 kV voltage classes, insulation withstand values, busbar current classes and cabinet weight.

Rated voltage3, 6, 7.2, 12, 24 kV
1 min power-frequency withstand voltage42 kV
Lightning impulse withstand voltage75 kV
Rated frequency50 Hz
Main busbar rated current630/1250/1600/2000/2500/3150/4000/5000/6300 A
Branch busbar rated current630/1250/1600/2000/2500/3150/4000/5000/6300 A
4 s thermal stability current16/20/25/31.5/40/50 kA
Rated dynamic current peak40/50/63/80/100/125 kA
Protection levelShell IP4X; isolation room and circuit breaker compartment IP2X
Weight1000 kg
Cabinet construction

KYN28 Withdrawable VCB, Relay Chamber and Interlock System Specifications

The KYN28 structure combines a metal-clad body, withdrawable breaker truck, relay chamber, cable compartment and safety interlocking.

Cabinet constructionAir-insulated, metal-clad, withdrawable indoor switchgear
Main circuit dutyReceiving and distributing 3 kV to 24 kV network electrical circuits
Protection and monitoringRelay chamber supports microprocessor-based relay protection devices
Remote functionsRemote control, telemetry, communication and remote transfer through CAN communication interface
Interlock functionFive-anti interlocking to reduce breaker, handcart, grounding switch and live-space misoperation
Breaker optionsVS1(ZN63), ZN12 and VD4 vacuum circuit breaker options
Contactor optionVC series vacuum contactor
Cabinet viewsFront lineup, side enclosure and compartment interior views are available for construction review
01

System voltage

3.6/7.2/12 kV or 3-24 kV ratings

Use KYN28A-12 ratings for common 12 kV rooms. Check the extended KYN28 ratings when 24 kV class appears in the specification.

02

Rated current

630 A to 4000 A cabinet current

Match the cabinet current to incoming, transformer, feeder or bus-section duty before selecting the breaker truck.

03

Busbar current

Main and branch busbar to 6300 A

Confirm higher busbar classes before cabinet width, busbar bridge and lineup arrangement are fixed.

04

Fault level

16 kA to 50 kA for 4 s

Short-time withstand and peak withstand values must match the protection study and utility standard.

05

VCB model

VS1, ZN12, VD4 or VC contactor

Confirm the vacuum circuit breaker or contactor together with CT, PT, relay, trip circuit and auxiliary supply.

06

Room layout

Cable entry and operating clearance

Check cable trench, rear access, grounding switch position, door swing and switch room clearance before production drawings.

Site conditions

KYN28 Switchgear Application and Installation Conditions

Match KYN28 to the indoor MV room and site limits before final layout. This cabinet belongs in a switchgear room, not an outdoor compact network point.

01

Indoor MV switchgear room

Use KYN28 for incoming, outgoing, transformer feeder, bus-section and metering cabinets in indoor medium-voltage rooms.

02

Substation distribution

Use KYN28 where withdrawable breaker trucks, relay chamber access and metal-clad compartment separation are required.

03

Industrial plant power room

Select KYN28 for plant MV distribution after confirming fault level, VCB duty, cable entry and maintenance access.

04

Commercial building MV room

Use KYN28 when room clearance, cable trench and operation aisle can support withdrawable switchgear.

Testing and delivery

KYN28 Switchgear Drawings, Routine Tests and Packing

After ratings and breaker model are fixed, confirm the drawings, routine verification and packing details before production release and shipment.

01

General arrangement drawing

Cabinet lineup, overall dimensions, cable entry, foundation reference, busbar position and room clearance. Confirm width, depth and height from the GA drawing before civil work.

02

SLD and wiring drawings

Incoming and outgoing circuits, CT/PT, relay protection, metering, auxiliary control and terminal wiring.

03

Routine verification

Power-frequency withstand, insulation, mechanical operation, interlock, protective circuit and nameplate checks.

04

Packing and handling

Cabinet split, lifting point, moisture protection, packing marks, wooden case or pallet and destination standard.

When should KYN28 be selected instead of RMU?

Use KYN28 when the project needs indoor MV feeder cabinets with withdrawable breaker trucks, relay chambers and switch room access. Use RMU for compact cable ring networks and secondary distribution.

What voltage range can be covered by KYN28?

The KYN28A-12 ratings cover 3.6 kV, 7.2 kV and 12 kV. The extended KYN28 ratings list 3, 6, 7.2, 12 and 24 kV classes, which should be checked against the project standard.

Is KYN28 suitable for outdoor installation?

KYN28A-12 is specified for indoor switchgear rooms. Outdoor feeders should be checked against RMU, prefabricated substations or outdoor cabinet scope.

How is KYN28 different from XGN fixed-type switchgear?

KYN28 uses a withdrawable breaker truck and metal-clad compartment arrangement. XGN fixed-type switchgear is reviewed when the project prefers a fixed cabinet layout instead of withdrawable VCB maintenance.

What should be sent for a KYN28 quotation?

Send the single-line diagram, rated voltage, rated current, busbar current, short-circuit level, VCB model, CT/PT, relay and metering plan, cable entry, room layout, quantity and destination standard.

Project-based quotation

Request a KYN28A-12 Metal-Clad Switchgear Quote

Send the single-line diagram, voltage class, rated current, busbar current, short-circuit level, VCB model, relay and metering plan, cable entry, room layout, quantity and destination standard. XIYA POWER will return the rating confirmation, VCB and relay package, drawing list, packing method and commercial quotation.