Internal Arc Classification for MV Switchgear: IAC AFL/AFLR, Access, and Project Inputs

Switchgear internal arc classification AFL AFLR is common RFQ shorthand, but selection requires a complete declaration, not a catalogue label. Define who can access the installation, which enclosure sides remain accessible, the project arc current and duration, the exact lineup/compartment configuration, and the room pressure-relief conditions. Then require evidence that maps those conditions to the offered assembly.

Visual disclosure: all images are generated illustrative technical visualizations, not XIYA POWER factory, design, test, FAT, manufacturing, installation, commissioning, or field photographs.

Decode the Complete IAC Declaration Before Comparing Offers

Internal arc classification (IAC) under IEC 62271-200 describes a metal-enclosed switchgear assembly tested under defined internal-arc conditions. The declaration combines the accessibility type, classified sides, prospective arc current, and arc duration. All elements are needed for comparison.

A complete example is IAC AFL 20 kA, 0.5 s. Schneider Electric’s official IAC accessibility FAQ explains the public notation. Type A restricts access to authorized personnel; F/L designate the front/lateral classified sides; 20 kA is the stated current; and 0.5 seconds is the stated duration. The same source defines types B/C and the R rear-side designator. Clause-level requirements remain controlled by the purchased standard, project specification, and configuration-applicable manufacturer evidence.

Declaration element Example Selection meaning Hold condition
Classification prefix IAC Internal arc classification is declared Prefix missing or replaced by marketing wording
Accessibility type A Access restricted to authorized personnel Project access model not matched
Classified sides FL Front and lateral sides are included An accessible side is omitted
Arc current 20 kA Stated prospective arc current for the test Project fault basis or evidence missing
Arc duration 0.5 s Stated duration for the test Protection clearing basis unresolved

`

Complete IAC declaration elements for accessibility sides current and duration
Illustrative technical visualization: accessibility type, classified sides, arc current, duration, and applicable evidence form one complete IAC declaration.

`

A bare AFL or AFLR is incomplete without current, duration, and applicable evidence. The Complete Switchgear Cabinets owner provides family context, but no family name proves an IAC declaration for every bay, compartment, or installation arrangement.

Select Accessibility Type and Classified Sides From the Operating Model

Accessibility type describes who may be near the enclosure under the defined installation and operating model:

  • Type A: restricted to authorized personnel only.
  • Type B: unrestricted accessibility, including the general public.
  • Type C: restricted by installation out of reach above a public area; F/L/R side designators do not apply in the same way.

For types A and B, F is front, L is lateral, and R is rear. The manufacturer identifies the front of the equipment. The project identifies which faces people can occupy or reach during energized service, switching, inspection, or work on an isolated compartment while adjacent equipment remains energized.

Project access condition Required input Decision Supplier return Hold condition
Front operating aisle only Room plan and access rules Confirm front-side requirement Complete IAC code and evidence Other sides are not demonstrably inaccessible
Front plus lineup-end access End-panel and barrier arrangement Include lateral-side review F/L classification mapping End condition absent from evidence
Rear corridor occupied while lineup/adjacent bays remain energized Rear access and operating states Rear side must be resolved Applicable R evidence or accepted access redesign AFL offered with accessible rear
Public presence near enclosure Occupancy and barriers Review type B or C need Type/accessibility declaration Type A is assumed without control

The difference between AFL and AFLR is therefore not cosmetic. AFL includes front and lateral sides; AFLR also includes rear. If the rear remains accessible under an energized operating state, the project needs an applicable rear-side solution or a reviewed physical/access redesign that genuinely removes that exposure.

`

Front lateral and rear switchgear access paths for AFL and AFLR review
Illustrative technical visualization: front, lateral, and rear occupancy under energized service determines whether the project must resolve AFL or AFLR coverage.

`

The fixed-versus-withdrawable decision changes compartments, access routes, and maintenance states, but does not by itself assign IAC. Use the XGN versus KYN28 project-fit guide for that upstream architecture decision, then apply the actual room and operating model here.

Match Arc Current and Duration to the Project Fault and Protection Basis

Derive the required arc current and duration from current project sources. Current inputs come from the short-circuit study at the switchgear location, including applicable source contributions and operating configurations. Duration inputs come from the approved protection clearing basis, including the relevant primary and backup scenario defined by the project risk model.

Utility rules and the project specification may set additional requirements. Record each value’s source, revision, system state, and owner. Do not select an IAC current/duration from a catalogue maximum or a previous project.

Input Required source Supplier comparison Release evidence
Prospective arc current Current short-circuit study and operating configuration Offered IAC current is not below the specified value Report/declaration for exact configuration
Arc duration Protection clearing basis and project rule Offered duration is not below the specified value Applicable test duration and protection reference
Accessibility/side requirement Room, barriers, occupancy, and operating states Offered code covers every required side/type Side mapping and installation evidence
Variant/configuration Bay schedule, compartments, end panels, relief system Offered assembly remains within evidence scope Applicability matrix and deviations

A numerically higher current or longer duration is not sufficient by itself. It cannot repair a missing classified side, wrong accessibility type, different pressure-relief arrangement, or inapplicable report. The MV switchgear RFQ data guide owns the wider SLD, bay, fault-duty, room, and protection input package.

Coordinate the Switchgear, Room, and Pressure-Relief Path as One Installation

Internal-arc evidence is obtained with defined equipment and installation conditions. The project must show that the offered lineup and room replicate those conditions or remain within a documented applicability boundary.

Installation input Project return Evidence question Hold condition
Wall or free-standing arrangement Dimensioned room/GA Was the same arrangement represented? Arrangement differs without review
End panels and lineup length Bay schedule and end treatment Are ends and representative cubicles covered? End/lineup scope unclear
Compartments and bay variants Configuration schedule Which internal-arc test locations apply? Variant inferred from family name
Doors, covers, and relief flaps Operating-state schedule Does the tested state match normal service? Required part/state omitted
Plenum or pressure-relief duct Duct drawing and exhaust destination Does the evidence include this route? Duct/vent path not mapped
Ceiling, wall, and side clearances Coordinated room drawing Are clearances within evidence conditions? Geometry is outside the record
Cable trenches and floor openings Civil/interface drawing Was opening treatment represented? Uncontrolled exhaust path remains
Occupied areas Access and barrier plan Are hot gases routed away from people? Exhaust reaches an occupied path

`

Switchgear room pressure relief and IAC evidence applicability inputs
Illustrative technical visualization: lineup variants, end panels, compartments, doors, ducts, clearances, trenches, and occupied routes must remain inside the evidence boundary.

`

Manufacturer data should identify the tested object, lineup arrangement, compartments, relief system, room conditions, and exclusions. A different end panel, open trench, ceiling height, duct, or exhaust destination can change applicability even when the cabinet type code is unchanged.

For one common family, the KYN28 switchgear specification assigns classification, compartment, interlock, and room-interface inputs to the exact panel schedule. CAB-07 does not infer IAC from the KYN28 name; it requires the offered configuration’s evidence.

Require Configuration-Applicable Evidence and State What IAC Does Not Prove

Issue an IAC RFQ checklist and data pack that normalizes every supplier return:

  1. Exact family, type designation, rating schedule, bay types, and compartments.
  2. Complete IAC code: accessibility type, F/L/R sides, current, and duration.
  3. Test report or declaration reference, laboratory, date, and tested object.
  4. Lineup length, representative cubicles, end-panel configuration, and test locations.
  5. Doors/covers state, pressure-relief flaps, plenum/duct, and exhaust destination.
  6. Wall/free-standing arrangement, clearances, cable trench/opening treatment, and barriers.
  7. Applicability matrix from the tested object to every offered variant.
  8. Deviations, exclusions, engineering review status, and required release evidence.

Normalize each return against the same project rows. Mark an entry as a project requirement, supplier declaration, report result, applicability statement, deviation, or unresolved assumption. Record the source revision and affected bays beside it. This prevents a compliant headline on one representative cubicle from being reused silently for a different end panel, compartment, duct, or lineup arrangement.

An IAC report is not an insulation test record. The insulation resistance versus power-frequency withstand guide explains those two tests and their different outputs. Neither proves IAC, and IAC does not replace either where required.

IAC also does not prove that an internal arc cannot occur, that no injury is possible, or that equipment remains serviceable afterward. It does not establish LSC, partition class, IP rating, general fault duty, insulation level, interlock performance, earthing, pressure-relief adequacy for a different room, or every variant in a product family. Avoid arc-proof; use internally arc classified for the stated type, sides, current, duration, configuration, and installation conditions.

The complete FAT evidence pack, routine reports, deviations, retests, and final release records are a separate downstream activity. CAB-07 defines the IAC selection evidence that must enter that later pack.

Hold an Illustrative AFL Offer With an Accessible Rear Corridor

Representative engineering review, not a XIYA POWER customer, factory, design, test, FAT, installation, commissioning, or field case. All values and room conditions are illustrative and non-universal.

A 12 kV lineup has a project input of 20 kA and a protection clearing basis of 0.7 s. The supplier headline is IAC AFL 25 kA, 1 s. The room has a 1,500 mm front operating aisle, 800 mm lateral access at the lineup end, and an 800 mm rear cable corridor. Authorized personnel may use the rear corridor while adjacent bays remain energized.

Required input Decision Supplier return Release evidence Hold condition
Type A access Authorized-only operating area A stated Applicable report required None at notation level
Project current/duration 20 kA and 0.7 s basis 25 kA and 1 s stated Exact configuration not yet mapped Numeric headline alone is insufficient
Accessible sides Front, lateral, and rear AFL; rear omitted No rear-side mapping Accessible rear is unclassified
End-panel arrangement Offered end condition must be covered Not confirmed Pending Evidence applicability open
Pressure-relief duct Offered duct/room path must be covered Not mapped Pending Installation applicability open

`

Illustrative AFL offer held because the rear corridor remains accessible
Illustrative technical visualization: an AFL-classified front/lateral offer remains on hold when the rear corridor and pressure-relief evidence are unresolved.

`

The apparently higher current and duration do not close the rear-side or evidence gaps. Decision: hold. Request an applicable AFLR offer that maps the rear side, end panel, compartments, and relief duct. Alternatively, complete a reviewed room/access redesign that genuinely removes rear accessibility during energized service. No final selection, design approval, test, FAT, installation, or release outcome is claimed.

Frequently Asked Questions

What does IAC AFL mean on MV switchgear?

It declares internal arc classification with accessibility type A and classified front/lateral sides. A complete declaration also states arc current and duration and requires evidence for the offered configuration.

What is the difference between IAC AFL and AFLR?

AFL covers front and lateral sides. AFLR also covers the rear. The project decides whether rear classification is required by reviewing actual room access, barriers, and energized operating states.

Does a higher IAC current automatically make an offer acceptable?

No. Current and duration must meet the specified basis, but accessibility type, classified sides, configuration, room/relief conditions, and evidence applicability must also close.

Does IAC prove the switchgear is arc-proof?

No. IAC is a classification under stated test conditions. It does not guarantee that an arc cannot occur, zero injury, access to unclassified sides, or post-event serviceability.

How do room layout and pressure relief affect IAC selection?

The room defines accessible sides and the exhaust path. End panels, clearances, ducts, flaps, trenches, barriers, and occupied areas must remain within the evidence conditions for the offered lineup.

What evidence should a supplier return for an IAC requirement?

Require the complete code, report/declaration, tested object, covered bays/compartments, end arrangement, relief route, installation conditions, applicability matrix, deviations, and release-evidence path.

Candy Zhao
Candy Zhao

Sales Director at XIYA POWER, coordinating technical RFQs for medium-voltage switchgear, load break switches, disconnect switches, fuse cutouts, surge arresters and related distribution equipment. Candy Zhao supports quotation communication, drawings, test report requests, delivery basis and export order details for utilities, EPC contractors, panel builders and distributors.

Articles: 61